* Specifications
Pipe Range : >12.7mm up to 4.5m
Power Input : 100–240VAC, 50/60Hz, 10VA max
Flow Rate Range : 0.03m/s to 12.2m/s in most applications
Accuracy : +/-2% of reading or 0.03m/s whichever is greater.
Requires solids or bubbles of minimum size 100 microns, minimum concentration 75ppm
Repeatability : +/- 0.1%
Linearity : +/-0.5% of full scale
Display : White, backlit matrix – displays flow rate, relay states, 16-digit Totaliser, operating mode and calibration menu
Output : Isolated 4–20mA (1000 ohm load max.) or 0-5VDC (Field Selectable)
Control Relays : Qty 2, rated 5 amp SPDT, programmable flow alarm and/or proportional pulse
Data Logger : Standard built-in 26 million point logger with USB output and Windows software
Enclosure Watertight, dust tight; NEMA4X (IP 66} polyester with a clear polycarbonate face
Electronics Operating Temp : -23°C to +60°C
Sensor Operating Temp : -40° to +150°C (-40° to 300°F)
Options :
Industrial Automation Protocols : Modbus RTU via RS485 or HART (field selectable)
Sensors : Intrinsic Safety Barriers for mounting in hazardous locations contact Micronics
Enclosure Heater : 9-32VDC. Enclosure Heater and Thermostat for outdoor installation.